Sitemap
power watch

120V Voltage Disturbance Recorder

PowerWatch Model 001
Frequency Range: 45 to 65 Hz.
Frequency Resolution: 0.1 Hz.
Frequency Accuracy: +/-0.1 Hz. (3 cycles minimum)
Memory Size: 4,000 events.
Common Specifications: See Common Specs
Software: See Software
PDF: View PDF
Surge, Sag & Outage Hot to Neutral Neutral to Ground
Range 0 to 200 V rms 3 to 200 V rms
Accuracy +/-1 V rms + resolution +/-1 V rms + resolution
Resolution: 1 V rms 1 V rms
Impulse Hot to Neutral Neutral to Ground
Range: 100 to 2500 V peak 50 to 2500 V peak
Accuracy: +/-10% of reading + resolution +/-10% of reading + resolution
Resolution: 10 V 10 V
Width Detection: 1 msec minimum 1 msec minimum
Phase Angle Accuracy: +/-1° (20 to 180°, 200 to 360°) +/-1° 20 to 180°, 200 to 360°)
Phase Angle Resolution:
Time Events (<1 sec) Hot to Neutral Neutral to Ground
Accuracy: +/-0.5 cycle +/-1 cycle
Resolution: 0.5 cycle 1 cycle
Time-stamp Accuracy: +/-2 sec./day + resolution
Time-stamp Resolution: 8 seconds

$640.00

 

220/240V, 50/60 Hz Voltage Disturbance Recorder

PowerWatch Model 002
Frequency Range: 45 to 65 Hz.
Frequency Resolution: 0.1 Hz.
Frequency Accuracy: +/-0.1 Hz. (3 cycles minimum)
Memory Size: 4,000 events.
Common Specifications: See Common Specs
Software: See Software
PDF: View PDF
Surge, Sag & Outage Hot to Neutral Neutral to Ground
Range 0 to 400 V rms 0 to 50 V rms
Accuracy +/-2 V rms + resolution +/-.25 V rms + resolution
Resolution: 2 V rms .25 V rms
Impulse Hot to Neutral Neutral to Ground
Range: 100 to 2500 V peak 50 to 2500 V peak
Accuracy: +/-10% of reading + resolution +/-10% of reading + resolution
Resolution: 10 V 10 V
Width Detection: 1 msec minimum 1 msec minimum
Phase Angle Accuracy: +/-1° (20 to 180°, 200 to 360°) +/-1° (20 to 180°, 00 to 360°)
Phase Angle Resolution:
Time Events (<1 sec) Hot to Neutral Neutral to Ground
Accuracy: +/-0.5 cycle +/-1 cycle
Resolution: 0.5 cycle 1 cycle
Time-stamp Accuracy: +/-2 sec./day + resolution
Time-stamp Resolution: 8 seconds

$640.00

 

(800) 576-6308 or email for Application Assistance    

Storage Method: First-in, First-out or Fill-then-stop.
Size: 85 mm x 68 mm x 35 mm. (3.35" x 2.65" x 1.35").
Weight: 4 ounces (120 grams).
Case Material: Noryl® Plastic.
Operating Limits: 40°C to 70°C (-40°F to 158°F); 0 to 95% RH (non-condensing).
Battery: 3.6 Volt Lithium.
Battery Life: 10-years warrantied (under normal use). Factory replaceable.
Memory Size: 32 K, 4000 events.
Sampling Method: Continuous (half cycle integrated).
Alarm Type: Optical; Red LED.
PDF Click Here
Fuse: 1/16A fast-blow; (non-replaceable).
PC Requirements: IBM PC or 100% compatible running MS Windows 3.1,95,98, or NT, with a least 2 MB RAM, 2 MB of hard drive disk space and one free serial port.
Certifications: CSA; NRTL/C; UL1244.
Event Types Detected: Surges, sags, impulses, dropouts, outages, frequency variations.
Measurement Locations: Hot to Neutral. Neutral to Ground.
Plug Configurations: North America (120 Volt). Australia (240 Volt). United Kingdom (240 Volt). Continental Europe (240 Volt).

 

 

callCall - (800) 576- 6308 or Mail for assistance
create facebook
- © FLW, Inc 1997- - S.D.G.