AC
Phase Angle Input Modbus or Laurel ASCII Protocol Serial I/O Transmitter
|

|

For angular phase offset in degrees of AC waveforms.
DIN Rail mounted, digitally programmable.
|
Click
to Order AC Phase Angle Input
|
|
Features
|
Selectable Modbus or Laurel ASCII protocol. |
Modbus
RTU or ASCII modes, 2-wire connection, up to 247 digital
addresses. |
| Compliant
with Laurel ASCII protocol (selectable). |
Transmits
phase angle between two AC waveshapes of similar period. |
| Frequency
from .005 Hz to 10 kHz. |
Resolution
of 1º, 0.1º or 0.01º |
| 01%
accuracy at AC line frequency. |
Converts
phase input to six-digit reading:
- Digital span adjust from 0 to ±999,999.
- Digital zero adjust from -999,999 to +999,999. |
| Inputs
from NPN or PNP proximity switches, contact closures,
digital logic, magnetic pickups down to 12 mV, or AC
inputs up to 250 Vac. |
Triggers
on positive or negative pulse edges. |
| 5V,
10V or 15 V dc excitation output to power sensors. |
DIN rail mount package only
22.5 mm thick. |
| Detachable
screw clamp plug connectors |
Easy setup using Laurel's
PC-based Instrument
Setup Software. |
|
|
Description
|
|

The
serial output of Laureate AC phase angle
transmitter
indicates the lead or lag in degrees
from 0º to 360º between two periodic
signals having the same period. In the
illustration to the left, phase angle is
360*P1/P. The signals are applied to the
Channel A and B inputs of the Laureate
dual-channel pulse input signal
conditioner board.
Phase
angle measurement is commonly used with
AC power from 50 Hz to 400 Hz. Phase
angle needs to be set to zero to
synchronize AC generators. It also
applies to the triggering of SCRs and
Triacs for power control. The phase
angle between AC current and voltage
determines power factor. The Laureate
phase angle meter and transmitter
provide exceptionally fast response and
high accuracy for low frequencies, such
as AC line frequency.
Phase
angle measurement with the Laureate
phase angle meter or phase angle
transmitter requires that two signals
with identical periods be applied to
Channels A and B. A display from -180º
to +180º is obtained by timing the
rising edge of one channel and the
falling edge of the other channel, and
programming a 180º offset. A resolution
of 1º, 0.1º or 0.01º is selectable.
Accuracy is 0.01% up to 100 Hz, 0.1% at
1 kHz, and 1% at 10 kHz.

Phase
angle is determined by timing crystal
clock pulses over a specified gate time
which is selectable from 10 ms to 199.99
s. By selecting the minimum gate time of
10 ms, the update rate can be up to 20/s
for 50/60 Hz AC line frequency. Improved
accuracy is obtained by making the gate
time long enough so that multiple cycles
can be averaged.
Serial
Data I/O & Programming
Laureate
TM Series transmitters send data as a
serial digital signal. RS485 or RS232
signal levels are jumper selectable and
can each be associated with either the
Modbus protocol or Laurel’s simpler
Custom ASCII protocol.
- Modbus
protocol operation is
fully compliant with the Modbus Over
Serial Line Specification V1.0
(2002) for 2-wire, half-duplex
connection. This includes RTU or
ASCII modes, addressing of up to 32
devices per RS485 line without a
repeater, and up to 247 digital
addresses. Modbus operation allows
devices by different manufacturers
to be connected in parallel and be
addressed using the same protocol.
- Laurel’s
Laurel ASCII protocol
allows up to 31 Laureate
devices to be addressed on the same
RS485 data line. It is simpler than
the Modbus protocol and is
recommended when all devices are
Laureates. It also allows use of
Laurel’s datalogging software.
Transmitter
programming is
via the unit's three-terminal serial
port using Laurel's PC-based Instrument
Setup Software. This software can be
downloaded from this website at no
charge. The required transmitter-to-PC
interface cable is available from Laurel
(P/N CBL03). Laurel's Serial I/O
transmitters and meters can also be part
of PC-based data logging systems using
Laurel's Datalogging
Software, which operates under the
Laurel ASCII Protocol. A single software
command switches between the Modbus and
Laurel ASCII Protocols.
Transmitter
Options
Options
include dual solid state relays for
local alarm or control and an isolated
4-20 mA or 10V (selectable) analog
output, effectively providing a
linearized analog transmitter output
that tracks the reading that would be
transmitted digitally. The analog output
provides 12-bit (4096 step) resolution
of the output span and is ultra-linear
to within one bit. Its accuracy is ±0.05%
of span for all signal types, except for
AC rms, where accuracy is ±0.1%. Output
isolation from signal and power grounds
is provided by a separate on-board power
supply, which can drive 20 mA into a 500
ohm load for 10V compliance. Output
isolation eliminates problems caused by
ground loops.
DIN
Rail Mounting
Laureate
transmitters are housed in a 35 mm DIN
rail case that is only 22.5 mm
(0.89") thick. Signal connections
are via detachable screw clamp plug
connectors.
|
|
|
Click
to Order AC Phase Angle Input
|
|
General
Specifications
|
|
Pulse Input |
Types
Signal Ground
Minimum Signal
Maximum Signal
Maximum Frequency
Contact Debounce |
AC, pulses from NPN, PNP
transistors, contact closures, magnetic pickups.
Common ground for channels A & B.
Nine ranges from (-12 to +12 mV) to (+1.25 to +2.1V).
250 Vac
1 MHz, 30 kHz, 250 Hz (selectable).
0, 3, 50 ms (selectable). |
|
Phase Angle Operation |
Item Transmitted
Digital Resolution
Transmitted Units
Frequency Range
Accuracy
Maximum Timing Interval |
Phase angle difference between two waves of
same period
6 digits
1°, 0.1°, 0.01°
0.005 Hz to 10 kHz
0.01°, 0.005 Hz to 100 Hz; 0.1° at 1 kHz, 1° at 10 kHz
200 s |
|
Update Rate |
Conversion Interval
Gate Time
Time Before Zero Output |
Gate time + 30 ms + 0-2 signal periods
Selectable 10 ms to 199.99 s
Selectable 10 ms to 199.99 s |
|
Serial I/O (standard) |
Signal levels
Data Rates
Output Isolation
Serial Protocols
Devices on RS-485 Line
Modbus Addresses
Modbus Modes
Modbus Compliance |
RS485 (default) or RS232 (jumper selectable)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test.
Modbus RTU, Modbus ASCII, Laurel ASCII (selectable)
32 max without a repeater.
247 max
RTU or ASCII, 2-wire.
Modbus over Serial Line Specification V1.0 (2002). |
|
Transducer Excitation
Output (standard) |
Jumper Selection 1
Jumper Selection 2
Jumper Selection 3 |
10V @ 60 mA, isolated to 50V from signal
ground
5V @ 50 mA, isolated to 50V from signal ground
15V @ 60 mA, non-isolated |
|
Dual Relay Output
(optional) |
Relay Type
Load rating |
Two solid state relays, SPST, normally open,
Form A
120 mA at 130 Vac or 170 Vdc, 28 ohms series resistance. |
|
Analog Output
(optional) |
|
Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation |
0-20 mA, 4-20 mA or 0-10 Vdc
(selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kOhm load )
12 bits (4,096 steps)
±0.05% of output span
250V rms working, 2.3 kV rms per 1 minute test |
|
Power Input |
|
Standard power
Low power option
Frequency
Power Isolation |
95-240V AC ±10% or 90-300V DC
12-30V AC or 10-48V DC
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test. |
|
Mechanical |
|
Case Dimensions
Case Mounting
Electrical Connections |
120 x 101 x 22.5 mm
35 mm rail per DIN EN 50022
Detachable screw clamp plug connectors |
|
Environmental |
|
Operating Temperature
Storage Temperature
Relative Humidity |
0°C to 70°C
-40°C to 85°C
95% at 40°C, non-condensing |
|
Using
Laureate Meters, Counters and Transmitters to Synchronize Motor
Generators
|
|

|
Synchronization of two motor
generators requires that the two frequencies be identical, that
the lines be in phase, and that the line voltages be close to
each other. In this illustration, a single Laureate dual channel
counter (or frequency transmitter) measures both frequencies to
six-figure accuracy in a few line cycles. Another Laureate dual
channel counter (or phase transmitter) measures phase angle to
0.1º resolution. Two Laureate AC RMS Voltmeters, which offer
ranges of 200.00 V and 600.0 V, are used to display the two RMS
voltage to 0.1% accuracy.
|
|
|
|
|
|