Sum, Difference, Ratio, Product for Rate or Total with 2 Input Channels


Serial ASCII or Modbus Transmitter for Sum, Difference, Ratio, Product of 2 Pulse Input Signals
Modbus or Laurel ASCII Protocol Serial I/O Transmitter
 DIN Rail mounted, digitally programmable.


Click to Order Transmitter for Sum, Difference, Ratio, Product of 2 Pulse Input Signals


Features
Standard Main Board

Selectable Modbus or Laurel ASCII protocol.
Modbus RTU or ASCII modes, 2-wire connection, up to 247 digital addresses.
Two independently field-scalable pulse input channels. Internal conversion of Channel A & B inputs to six-digit readings:
- Digital span adjust from 0 to ±999,999.
- Digital zero adjust from -999,999 to +999,999.
Applicable arithmetic functions: A+B, A-B, AxB, A/B, A/B-1 (draw). Frequencies from 0.005 Hz to 1 MHz.
Inputs from NPN or PNP proximity switches, contact closures, digital logic, magnetic pickups down to 12 mV, or AC inputs up to 250 Vac High output update rate.
Square root extraction standard. Isolated 5V, 10V or 15V dc excitation output to power transducers.
DIN rail mount package only 22.5 mm thick. Detachable screw clamp plug connectors.
Easy setup using Laurel's PC-based Instrument Setup Software. Optional dual solid state relays for alarm or control.

Description

Two-Channel Operation

Laureate TM Series serial output, pulse input transmitters accept two independently scalable input channels A & B from a wide range of pulse sources, such as NPN or PNP proximity switches, contact closures, digital logic, magnetic pickups down to 12 mV, or AC voltages to 250 Vac. Input frequencies can range from 0.005 Hz to 1 MHz. With the Standard main board, the transmitter output can be programmed to track rate or total for both channels. With the Extended main board, as used in the transmitters being presented in this web page, the transmitter output can also be programmed to track the sum, difference, product, ratio, or draw of both channels: A+B, A-B, AxB, A/B, A/B-1. These arithmetic operations can be applied to scaled rates, scaled totals, square root of rates, totals after square root extraction, custom curve linearized rates, or totals after custom curve linearization.

  • Sum can be used to add two flows for total flow, or to add parts carried by two conveyor belts.
      
  • Difference can be used to subtract outflow from inflow for net flow, or to subtract reject parts from total parts.
      
  • Product can be used to multiply two rates, for example to compute  horsepower by multiplying torque by RPM.
      
  • Ratio can be used to compare flow rates in two channels, the RPM of rollers or gears, or the speed of moving machinery, such as conveyor belts. Ratio can also be applied to scaled totals to compare two batches to be mixed. In this application, one transmitter is used to monitor the ratio of flow rates, and a second transmitter to monitor the resulting batch totals.
      
  • Draw is obtained by subtracting 1 from ratio. Draw is used to measure the elongation of material as it passes between rollers, or to monitor variation in the speed of rollers for tensioning.

Exceptional Accuracy and Stability

Dual Channel Pulse Input Signal conditioner BoardLaureate pulse input frequency and rate transmitters determine frequency by taking the inverse of period as measured with a calibrated quartz crystal time base. This results in extremely accurate and stable 6-digit internal readings (±999,999 counts), which are then processed in software. The output update rate is a programmed gate time + 30 ms + 0-2 signal periods. For a 60 Hz signal, the update rate would be 20 per second. Such fast update rates are ideal for alarm and control applications.

Serial Data I/O & Programming

Laureate TM Series transmitters send data as a serial digital signal. RS485 or RS232 signal levels are jumper selectable and can each be associated with either the Modbus protocol or Laurel’s simpler Laurel ASCII protocol.

  • Modbus protocol operation is fully compliant with the Modbus Over Serial Line Specification V1.0 (2002) for 2-wire, half-duplex connection. This includes RTU or ASCII modes, addressing of up to 32 devices per RS485 line without a repeater, and up to 247 digital addresses. Modbus operation allows devices by different manufacturers to be connected in parallel and be addressed using the same protocol.
     
  • Laurel’s Laurel ASCII protocol allows up to 31 Laureate devices to be addressed on the same RS485 data line. It is simpler than the Modbus protocol and is recommended when all devices are Laureates. It also allows use of Laurel’s datalogging software.

Transmitter programming is via the unit's three-terminal serial port using Laurel's PC-based Instrument Setup Software. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from Laurel (P/N CBL03). Laurel's serial output transmitters and meters can also be part of PC-based data logging systems using Laurel's Datalogging Software, which operates under the Laurel ASCII Protocol. A single software command switches between the Modbus and Laurel ASCII Protocols.

Transmitter Options

Options include dual solid state relays for local alarm or control and an isolated 4-20 mA or 10V (selectable) analog output, effectively providing a linearized analog transmitter output that tracks the reading that would be transmitted digitally. The analog output provides 12-bit (4096 step) resolution of the output span and is ultra-linear to within one bit. Its accuracy is ±0.05% of span for all signal types, except for AC rms, where accuracy is ±0.1%. Output isolation from signal and power grounds is provided by a separate on-board power supply, which can drive 20 mA into a 500 ohm load for 10V compliance. Output isolation eliminates problems caused by ground loops.

DIN Rail Mounting 

Laureate transmitters are housed in a 35 mm DIN rail case that is only 22.5 mm (0.89") thick. Signal connections are via detachable screw clamp plug connectors.

 


Click to Order Transmitter for Sum, Difference, Ratio, Product of 2 Pulse Input Signals


 

General Specifications

Pulse Input
Types

Ch A Frequency, Max
Ch B Frequency, Max
Signal Ground
Minimum Signal
Maximum Signal
Maximum Frequency
Contact Debounce
Time Base Accuracy
Arithmetic Functions

AC, pulses from NPN, PNP transistors, contact closures, magnetic pickups.

1 MHz.
250 kHz.
Common ground for channels A & B.
Nine ranges from (-12 to +12 mV) to (+1.25 to +2.1V).
250 Vac
1 MHz, 30 kHz,  250 Hz (selectable).
0, 3, 50 ms (selectable).
Quartz crystal calibrated to ±2 ppm.
A+B, A-B, AxB, A/B, A/B-1

Serial I/O (standard)

Signal levels
Data Rates
Output Isolation
Serial Protocols
Devices on RS-485 Line
Modbus Addresses
Modbus Modes
Modbus Compliance
RS485 (default) or RS232 (jumper selectable)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test.
Modbus RTU, Modbus ASCII, Laurel ASCII (selectable)
32 max without a repeater.
247 max
RTU or ASCII, 2-wire.
Modbus over Serial Line Specification V1.0 (2002).
Transducer Excitation Output (standard)
Jumper Selection 1
Jumper Selection 2
Jumper Selection 3
10V @ 60 mA, isolated to 50V from signal ground
5V @ 50 mA, isolated to 50V from signal ground
15V @ 60 mA, non-isolated
Dual Relay Output (optional)
Relay Type
Load rating
Two solid state relays, SPST, normally open, Form A
120 mA at 130 Vac or 170 Vdc, 28 ohms series resistance.
Analog Output (optional)  
Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation
0-20 mA, 4-20 mA or  0-10 Vdc (selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kOhm load )
12 bits (4,096 steps)
±0.05% of output span
250V rms working, 2.3 kV rms per 1 minute test
Power Input  
Standard power
Low power option
Frequency
Power Isolation
95-240V AC ±10% or 90-300V DC
12-30V AC or 10-48V DC
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test.
Mechanical  
Case Dimensions
Case Mounting
Electrical Connections
120 x 101 x 22.5 mm
35 mm rail per DIN EN 50022
Detachable screw clamp plug connectors
Environmental  
Operating Temperature
Storage Temperature
Relative Humidity
0°C to 70°C
-40°C to 85°C
95% at 40°C, non-condensing
 

Typical Applications

Controlling the Mixing Ratio of Two Fluids

Using a ratio meter or transmitter to control the mixing ratio of two fluids Transmitting and alarming the input flow rate ratio of two fluids (gas or liquid) allows these to be mixed in a predetermined ratio in continuous processes. The sensing element is normally a turbine flow meter, which outputs pulses at a frequency proportional to flow rate. The A/B ratio can also be transmitted for totalized rate (or delivered volume).

Comparing Fluid Inflow & Outflow

Using a ratio meter or transmitter to compare fluid inflow and outflow The ratio of the inflow and outflow rates of a tank is a measure of the relative filling or emptying rate. The same transmitter can also be programmed to transmit the net inflow or outflow rate in flow units, or to transmit totalized inflow our outflow in volume units. Any of these parameters can be alarmed using the dual relay board and be transmitted via 4-20 mA.

Controlling Coating Thickness on a Film

Using a ratio meter or transmitter to control coating thickness on a film In this application, Channel A measures the rate at which a coating material is applied, as measured by a flow meter, while Channel B measures the speed of the film based on pulses from a proximity switch. Transmitting and alarming the A/B ratio assures that an even thickness of coating material is applied as the speed of the film is varies.

Synchronizing Two Conveyor Lines

Using a ratio meter or transmitter to synchronize two conveyor lines The dual-channel Laureate transmitter can measure the speed of conveyor lines by using the output of proximity switches which sense gear teeth or spokes of rotating drive wheels. Transmitting the speed ratio of two lines allows line speeds to be adjusted so that material arrives at work stations when needed.

Measuring Draw for Elongation

Using a draw meter or transmitter to display and control elongation of film between rollers Draw (Ch A / Ch B - 1) can be used to indicate the elongation of films compressed between rollers, the shrinkage films, and the RPM difference of rollers whose speed is varied to maintain tension. The high resolution of Laureate dual channel transmitters is ideal for comparison of rates that are close to each other

 


Click to Order Transmitter for Sum, Difference, Ratio, Product of 2 Pulse Input Signals


Pinout
Laureate Serial Output Transmitters
Pulse Input for Frequency, Rate or Period
(shown with optional analog output and dual relay output)

Pinout, Serial ASCII or Modbus Transmitter for Sum, Difference, Ratio, Product of 2 Pulse Input Signals

                                   Transmitter Powering a Single Sensor
 

Pinout, Serial ASCII or Modbus Transmitter for Sum, Difference, Ratio, Product of 2 Pulse Input Signals

Pinout, Serial ASCII or Modbus Transmitter for Sum, Difference, Ratio, Product of 2 Pulse Input Signals
Transmitter Powering Two Sensors Transmitter with Active or Passive Sensors

Click to Order Transmitter for Sum, Difference, Ratio, Product of 2 Pulse Input Signals