Thermocouple & RTD Temperature
Modbus or Laurel ASCII Protocol Serial I/O Transmitter
|

|

Exceptional
linearity & accuracy at high update rates.
DIN Rail mounted, digitally programmable.
|
Click
to Order Thermocouple or RTD InputTransmitter
|
|
Features |
|
Selectable Modbus or Laurel ASCII protocol. |
Modbus
RTU or ASCII modes, 2-wire connection, up to 247 digital
addresses. |
| Also
compliant with Laurel ASCII protocol (selectable).
|
Input
for 100 ohm platinum RTDs with DIN and ANSI curves.
|
| 2,
3 or 4-wire RTD connection with lead resistance compensation.
|
Upscale
or downscale open sensor indication. |
| User
selectable spans from entire TC or RTD range down to 15.0°
|
Output
update rate to 60/sec. |
| Peak
value capture. |
DIN
rail mount package only 22.5 mm thick. |
| Detachable
screw terminal connectors. |
Easy
setup using Laurel's PC-based Instrument
Setup Software. |
| Optional
isolated scalable analog output (4-20 mA or 0-10V).
|
Optional dual solid state
relays for alarm or control. |
|
|
Description |
Signal
Conditioning for Thermocouples & RTDs
Signal
Types & Ranges. Laureate™ TM Series
serial output transmitters with the temperature
signal conditioner board provide a linearized,
highly accurate, stable and repeatable transmitter
output for multiple thermocouple types and 100
Ohm platinum RTDs. The meter accepts the outputs
of types J, K, T, E, N, R and S thermocouples,
plus 100 ohm platinum RTD’s with DIN alpha of
0.00385 and ANSI alpha of 0.003925. The thermocouple
or RTD type, unit of measure (°C or °F), resolution
(1° or 0.1°), and range are user selectable.
Cold
junction compensation automatically corrects
for temperature variations at the thermocouple
reference junction at the transmitters. Open
sensor indication is standard and may be set
up to indicate either upscale or downscale.
RTD excitation is provided by the transmitter.
RTD connections can be of the 2-, 3- or 4-wire
type. For 3- and 4-wire connections, the transmitter
automatically compensates for lead resistance
of the sensor.
All
ranges for all temperature sensor types are
digitally calibrated at the factory. This eliminates
the need for field calibration or drift caused
by potentiometers found in non-microcomputer
based devices.
All
Laureate analog input meters and transmitters
allow exceptionally fast read rates. Concurrent
Slope (Pat 5,262,780) is a method of analog-to-digital
conversion that allows up to 60 conversions
per second while integrating the input over
a full power cycle. Fast read rates provide
true readings and fast response for PID control
applications. Peak value capture is standard.
Full conversion accuracy is maintained in the
Modbus output.
Serial
Data I/O & Programming
Laureate
TM Series transmitters send data as a serial
digital signal. RS485 or RS232 signal levels
are jumper selectable and can each be associated
with either the Modbus protocol or Laurel’s
simpler Laurel ASCII protocol.
- Modbus protocol
operation is fully compliant with the Modbus
Over Serial Line Specification V1.0 (2002)
for 2-wire, half-duplex connection. This
includes RTU or ASCII modes, addressing
of up to 32 devices per RS485 line without
a repeater, and up to 247 digital addresses.
Modbus operation allows devices by different
manufacturers to be connected in parallel
and be addressed using the same protocol.
- Laurel’s
Laurel ASCII protocol allows up to 31 Laureate
devices to be addressed on the same RS485
data line. It is simpler than the Modbus
protocol and is recommended when all devices
are Laureates. It also allows use of Laurel’s
datalogging software.
Transmitter
programming is via the unit's three-terminal serial
port using Laurel's PC-based Instrument
Setup Software. This software can be downloaded
from this website at no charge. The required transmitter-to-PC
interface cable is available from Laurel (P/N CBL03).
Laurel's serial output transmitters and meters can
also be part of PC-based data logging systems using
Laurel's Datalogging
Software, which operates under the Laurel
ASCII Protocol. A single software command switches
between the Modbus and Laurel ASCII Protocols.
Transmitter
Options
Options
include dual solid state relays for local alarm
or control and an isolated 4-20 mA or 10V (selectable)
analog output, effectively providing a linearized
analog transmitter output that tracks the reading
that would be transmitted digitally. The analog
output provides 12-bit (4096 step) resolution
of the output span and is ultra-linear to within
one bit. Its accuracy is ±0.05% of span for all
signal types, except for AC rms, where accuracy
is ±0.1%. Output isolation from signal and power
grounds is provided by a separate on-board power
supply, which can drive 20 mA into a 500 ohm load
for 10V compliance. Output isolation eliminates
problems caused by ground loops.
DIN
Rail Mounting
Laureate
transmitters are housed in a 35 mm DIN rail case
that is only 22.5 mm (0.89") thick. Signal
connections are via detachable screw clamp plug
connectors
|
|
Click
to Order Thermocouple or RTD Input
Transmitter
|
| Description |
| TC
Type |
Range |
Conformity
Error |
| J |
-210°C
to +760°C
-347°F to +1400°F |
0.09°C
0.16°F |
| K |
-244°C
to +1372°C
-408°F to +2501°F |
0.1°C
0.17°F |
| T |
0°C
to +400°C
-257°C to 0°C
+32°F to 752°F
-430°F to +32°F |
0.03°C
0.2°C
0.05°F
0.36°F |
| E |
-240°C
to +1000°C
-400°F to +1830°F |
0.18°C
0.32°F |
| N |
-245°C
to +1300°C
-410°F to +2370°F |
0.10°C
0.17°F |
| R |
-45°C
to +1768°C
-49°F to +3214°F |
0.17°C
0.31°F |
| S |
-46°C
to +1768°C
-51°F to +3213°F |
0.12°C
0.22°F |
| Applicable
to all thermocouple types |
Calibration
Input resistance
Input current
Max lead resistance
Span tempco
Reference junction tempco
Span tempco
Overvoltage protection
NMR at 50/60 Hz
CMR, DC-60 Hz
CMV, DC-60 Hz
Open sensor indication |
NIST
Monograph 125 (IPTS-68)
1 Gohm
100 pA
1 Gohm max for rated accuracy
±0.003% of reading/ºC
±0.02 deg/deg
±0.003% of reading/ºC
125 Vac
80 dB plus selectable digital filter from
80 ms
to 9.6 s time constant
120 dB with 500 W imbalance
250 Vac from power and earth grounds
0 mA or > 20mA output, selectable |
Pt
100 RTD Input
| RTD
Alpha |
Range |
Conformity
Error |
DIN
.00385 |
-202°C
to +850°C
-331°F to +1562°F |
0.03°C
0.05°F |
ANSI
.003925 |
-202°C
to +631°C
-331°F to +1168°F |
0.04°C
0.07°F |
| Applicable
to all RTD types |
Calibration,
DIN
Calibration ANSI
Configuration
Excitation current
Span tempco
Zero tempco
Sensor lead resistance
tempco per conductor
Over-voltage protection
Open sensor indication |
IEC
751 (IPTS-68)
NIST Monograph 126
2, 3 or 4-wire connection
0.2 mA
±0.003% of reading/ºC
±0.03 deg/deg
2-wire, 10 mdeg/W/deg up to 10 W
3 & 4-wire, 10 mdeg/W/deg up to 100 W
125 Vac
0 mA or > 20mA output, selectable |
Thermocouple
& RTD
| Serial
I/O (standard) |
Signal
levels
Data Rates
Output Isolation
Serial Protocols
Devices on RS-485 Line
Modbus Addresses
Modbus Modes
Modbus Compliance |
RS485
(default) or RS232 (jumper selectable)
300, 600, 1200, 2400, 4800, 9600, 19200
baud
250V rms working, 2.3 kV rms per 1 min test.
Modbus RTU, Modbus ASCII, Laurel ASCII (selectable)
32 max without a repeater.
247 max
RTU or ASCII, 2-wire.
Modbus over Serial Line Specification V1.0
(2002). |
| Dual
Relay Output
(optional) |
Relay
Type
Load rating |
Two
solid state relays, SPST, normally open, Form
A
120 mA at 130 Vac or 170 Vdc, 28 ohms series
resistance. |
| Analog
Output
(optional) |
Output
Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation |
0-20
mA, 4-20 mA or 0-10 Vdc (selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kOhm load )
12 bits (4,096 steps)
±0.05% of output span
250V rms working, 2.3 kV rms per 1 minute
test |
| Power
Input |
Standard
power
Low power option
Frequency
Power Isolation |
95-240V
AC ±10% or 90-300V DC
12-30V AC or 10-48V DC
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test. |
| Mechanical |
Case
Dimensions
Case Mounting
Electrical Connections |
120
x 101 x 22.5 mm
35 mm rail per DIN EN 50022
Detachable screw terminal connectors |
| Environmental |
Operating
Temperature
Storage Temperature
Relative Humidity |
0°C
to 70°C
-40°C to 85°C
95% at 40°C, non-condensing |
Specifications
Laureate
Serial Output Transmitter, Thermocouple or RTD Input
(shown with optional analog output and dual
relay output)

Thermocouple
Transmitter Connection
RTD
Connections with Excitation & Lead Compensation
| |
Laureate
temperature transmitters
allow 2-, 3- or 4-wire RTD hookup to the
J5 connector. The transmitter applies an
excitation current of 0.2 mA, which it monitors
to make ratiometric corrections for excitation
supply variations.
In
2-wire hookup,
the transmitter senses the voltage drop
across the 100 ohm RTD and both lead wires.
The effect of the lead wires can be measured
and subtracted by shorting out the RTD during
transmitter setup.
In
3- and 4-wire hookup,
the transmitter senses the voltage drop
across the 100 ohm RTD and both lead wires
as well as the voltage drop across the RTD
and one lead wire. This allows the transmitter
to determine the effect of one lead wire
and mathematically subtract the effect of
both lead wires. |
| |
| |
| Operation
as a Fast ON/OFF Controller or Supervisory
Monitor
With
the optional dual solid state relay output
option, which has a typical response
time of only 17 ms, Laureate
temperature meters and transmitters can
serve as extremely fast and accurate ON/OFF
controllers for closed-loop temperature
control. They can
also serve as supervisory process monitors
and provide alarms or shutoffs when processes
exceed normal limits.
Multiple
setpoint operating modes are individually
selectable for each relay, as explained
in the dual-setpoint
controller page. Relay duty cycles
and chatter can be minimized with programmable
hysteresis and time delays. A band deviation
operating mode can be selected for each
relay, where an alarm is generated whenever
the reading is a selected number of counts
above or below the setpoint. With Modbus,
relay operation can be non-latching or
latching, with reset provided by digital
commands.
|
|