TS6
Serial-to-Analog DIN Rail Transmitter Converts
serial data to a scaled analog signal.
|

|
|
Click
to Order TS6 Serial to Analog DIN Rail Transmitter
|
|
Features |
| RS-232
or RS-485 serial input.
|
Choice
of 3 protocols: Modbus RTU, Modbus ASCII, or Laurel
ASCII.
|
| Able
to retrieve data from long character strings.
|
Data
rates from 300 to 19,200 bps.
|
| Isolated
4-20 mA or 0-10V transmitter output, user
selectable.
|
Analog
output resolution: 0.025% of span (12 bits).
|
| Analog
output accuracy: ±0.05%
of span.
|
Update
rate to 60/sec.
|
| DIN
rail mount package only 22.5 mm (0.89") thick.
|
Powered
by AC or DC.
|
| Detachable
screw-clamp connectors.
|
Powered
by 95-240V AC ±10% (standard) or low voltage AC or DC
(optional).
|
| Easy
setup using Laurel's PC-based Instrument
Setup Software.
|
Optional dual solid state
relays for alarm or control.
|
|
| Description
|
The
Laureate TS6 serial input to analog output
transmitter accepts RS-232 or RS-485 serial data
with Modbus or Laurel ASCII Protocols, and converts
it to an isolated, scalable 4-20 mA or 0-10V analog
output signal. The unit fits on a 35 mm DIN rail and
is only 22.5 mm (0.89") thick. It is normally
powered by AC (95-240V
ac ±10%), but can optionally be powered by low
voltage AC or DC. All electrical connections are via
detachable screw-clamp plugs.
Serial
Data Input
One three-screw-terminal connector
accepts RS-232 or RS-485 serial data, as selected
via jumpers on the main board. Data rates are
selectable as 300, 600, 1200, 2400, 4800, 9600 or
19200 bps. The RS-232 interface is suitable for
short cable runs and point-to-point communications.
The RS-485 interface is compliant with the EIA/TIA-485
standard and supports multiple addressable devices
on the same data line using the Modbus protocol or
Laurel ASCII Protocol. Modbus implementation is
fully compliant with Modbus over Serial Line
Specification V1.0 (2002) in RTU or ASCII, half
duplex (2-wire) operation, with up to 247 digital
addresses.
Selectable
Data Retrieval
The Laureate serial-to-analog
transmitter is able to retrieve digital data from
long character strings. You can specify character
positions, start and stop ASCII characters, how many
characters to skip, and how many characters to
process.
Analog
Transmitter Output
The
analog output is selectable as 0-10V or 4-20 mA
(also scalable for 0-20 mA). All selections provide
12-bit (0.025%) resolution of the output span and
are ultra-linear to within one bit. Accuracy is ±0.05%
of output span. Output isolation from signal, power
and serial communication grounds is provided by a
separate on-board transmitter power supply, thereby
eliminating potential problems caused by ground
loops. The supply can an drive 20 mA into a 500 ohm
(or lower) load for 10V compliance, or 10V into 5K
ohm (or higher) load for 2 mA compliance.
Easy
to Set Up and Install
Transmitter
programming is via a three-terminal RS-232 port
using Laurel's PC-based Instrument
Setup Software. This software can be
downloaded from this website at no charge. The
required transmitter-to-PC interface cable is
available from Laurel (P/N CBL03).
Laurel's transmitters
and meters can be part of PC-based data logging
systems using Laurel's Datalogging
Software, which operates under the Laurel
ASCII Protocol.
|
|
|
Click
to Order TS6 Serial to Analog DIN Rail Transmitter
|
|
Specifications
Laureate TS6 Serial-to-Analog DIN
Rail Transmitter
|
|
RS-232 Input Interface |
Data Rates
Devices on RS-232 line
Connector
Supported Protocols
Isolation |
300, 600, 1200, 2400, 4800, 9600, 19200 bps
1 (point-to-point, short distances)
Three detachable screw-clamp plugs: RXD, TCD, common
Modbus or Laurel ASCII
250V rms from power and analog output continuous, 2.3 kV rms per 1 min
test.). |
|
RS-485 Input Interface |
Cabling
Data Rates
Devices on RS-485 line
Connector
Standards Compliance
Supported Protocols
Isolation
|
Half duplex (2-wire)
300, 600, 1200, 2400, 4800, 9600, 19200 bps
32 max
Three detachable screw-clamp plugs: D0, D1, common
EIA/TIA-485
Modbus or Laurel ASCII
250V rms from power and analog output continuous, 2.3 kV rms per 1 min test. |
|
Modbus Protocol |
Type
Standards Compliance
Digital Addresses |
RTU or ASCII.
Modbus over Serial Line Specification V1.0 (2002).
247 max |
|
Laurel ASCII Protocol |
Type
Digital Addresses |
ASCII.
31 max |
|
Serial Input Electrical Protection |
ESD Protection
EMI Immunity
EFT Protection
Short Circuit Protection |
15 kV per IEC 1000-4-2
10 V/m per IEC 1000-4-3
2 kV per IEC 1000-4-4
Continuous |
|
Analog Output |
Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Isolation |
0-20 mA or 0-10 Vdc (selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kOhm load )
12 bits (4,096 steps)
±0.05% of output span
250V rms from power and serial I/O continuous, 2.3 kV rms per 1 min test |
|
Dual Relay Output
(optional) |
Relay Type
Load rating |
Two solid state relays, SPST, normally open,
Form A
120 mA at 130 Vac or 170 Vdc, 28 ohms series resistance. |
|
Power,
Electrical & Setup |
Power to Transmitter
Transmitter Setup
|
95-240V AC ±10% or 90-300V DC (standard power).
9-33V AC or 10-48V DC (low voltage power option).
Via RS-232 from PC using Instrument
Setup Software and CBL03 cable. |
|
Mechanical |
Case Dimensions
Case Mounting
Electrical Connections |
120 x 101 x 22.5 mm
35 mm rail per DIN EN 50022
Detachable screw-clamp plugs |
|
Environmental |
Operating Temperature
Storage Temperature
Relative Humidity |
0°C to 70°C
-40°C to 85°C
95% at 40°C, non-condensing |
|
|
|
|